Underfloor heating manifold with automatic flow control for 2 circuits

OEG no.: 512003977
Zoom Underfloor heating manifold with automatic flow control for 2 circuits

Underfloor heating manifold with Dynacon Eclipse inserts for reliable, simple and automatic hydraulic balancing.
For these manifolds, the flow rate for each heating circuit is set in l/h directly...

All product information Scope of delivery
AFC- Automatic Flow Control

AFC- Automatic Flow Control

AFC- Automatic Flow Control
Wipe 'n' Buy ®

Underfloor heating manifold with Dynacon Eclipse inserts for reliable, simple and automatic hydraulic balancing.
For these manifolds, the flow rate for each heating circuit is set in l/h directly at the valve with a turn for each heating circuit. The set flow rate is constantly maintained at the set value even if adjacent circuits are shut off. This means that closing or changing individual heating circuits does not have any impact on the total hydraulics. Generally, no additional fittings are necessary in the manifold.

The flow rate of each heating circuit can be continuously adjusted from 30 - 300 l/h.

The valves are fitted with high-quality EDPM gaskets. The included 3/4" end set allows for the system to be filled, drained or flushed easily.

The heating manifold is supplied preassembled on a wall bracket with pipe clamps.


Scope of delivery:
1 xheating manifold
1 xend piece set 1" IT
1 xWall bracket

For more information see Downloads


OEG no. 512003977
Material: Stainless steel
Type: HKV2013A-50-1"-AFC VA02
Wall distance [mm]: 16
Total length [mm]: 160
Length x Width x Height: 160 x 88 x 326.2 mm
Axial dimension: 50
Connection heating circuit: 3/4" Euro cone
Operating temperature [°C]: -5 .. 70
Valve connection: M30 x 1.5, 1/2"
Media: Water or water-glycol-mixture
Number of heating circuits: 2
Operating pressure max. [bar]: 10
Connection heat generator: 1" ET
EAN 4051394134907
Weight [kg] 1.8
Notes
AFC- Automatic Flow Control

AFC- Automatic Flow Control

AFC- Automatic Flow Control
Customs tariff number 84818059
en
Question (Number of heating circuits: 6)

Bonjour, est-ce que les raccords du collecteur sont en 3/4 euroconus et quel est le diamètre du collecteur même est-ce du 3/4 ou du 4/4 ? Merci de votre réponse.

Answer OEG:

Raccordement circuit de chauffage: Eurocône 3/4'' 

Raccordement du générateur de chaleur: 1'' FM

en
Question (Number of heating circuits: 6)

Beste, is deze ook geschikt voor koeling?

Answer OEG:

Ja, hij is geschikt voor de verwarmings-/koelwaterstroom van oppervlakteverwarming/-koeling conform DIN EN 1264-4.

en
Question (Number of heating circuits: 6)

Bonjour, Je ne vois pas bien les graduations, si je veux régler un circuit à 55l/h. Est ce possible de façon précise?

Answer OEG:

non, on peut seulement régler entre 40 et 60 l/h.

en
Question (Number of heating circuits: 6)

Bonjour, Est-ce que vous vendez des kits d'isolation (coques isolantes) pour ces collecteurs ? Bonne journée

Answer OEG:

Il n'y a pas d'isolation pour les collecteurs plancher chauffant, il existe des armoires pour ceux-ci (réf. Heating circuit manifold cabinet surface-mounted 760 mm et Heating manifold cabinet flush-mounted 760 mm par exemple).

You have to be logged in to ask a question