Leak detector, vacuum Eurovac NV 43755

OEG no.: 118307820
Zoom Leak detector, vacuum Eurovac NV

The Afriso Eurovac NV is a class I leak detector according to EN 13160 as a vacuum system for the safe monitoring of double or single-walled tanks with inner liners for the storage of non-flammable...

All product information
CE

CE

CE
Wipe 'n' Buy ®

The Afriso Eurovac NV is a class I leak detector according to EN 13160 as a vacuum system for the safe monitoring of double or single-walled tanks with inner liners for the storage of non-flammable and flammable liquids of hazard class A III (mineral oil products with flash point ≥ 55 °C) as well as AdBlue ® (urea solution 32.5 %) according to DIN 70070. In addition, Eurovac HV enables the monitoring of other media (e.g. waste and hydraulic oils, grinding coolants, brake fluid, etc.). The wide voltage range (AC 100 -240 V) allows problem-free use in different countries. The Eurovac is a compact leak detector in a robust wall-mounted housing with audible and visual alarm signalling; the audible alarm can be cancelled using the acknowledgement button. Eurovac NV maintains a low vacuum in the interstitial space of the tank. The vacuum pump is driven by an extremely economical DC motor (energy efficiency class A++) with a high starting torque. The Eurovac has a switching output for additional devices (e.g. additional alarm device ZAG 01, event signalling system EMS) or for integration into building management systems. The pump running time can be queried. With three hose connections (red, white, green) for pneumatic connection to the tank's interstitial space. The connection pieces can be used universally for 4 mm and 6 mm hoses. The sintered plastic filter in the condensate container indicates the current level of contamination and can be replaced quickly and easily from the outside if necessary. Electrical connection from above or below. A 9 V battery can be connected as an option so that an alarm is triggered in the event of a power failure.

  CE marking in accordance with EU Construction Products Regulation 305/2011, EU 574/2014, EN 13160-1/-2 and ÜHP


Technical data:
- Temperature application range: Ambient: -5/+50 °C
- Supply voltage: AC 100-240 V
- Nominal power: < 10 VA
- Switching output: Relay contact: 1 potential-free changeover contact
- Contact load: Max. 250 V, 2 A, ohmic load
- Operating pressure: Interstitial space: -60 to -85 mbar
- Wall-mounted housing made of impact-resistant plastic (ABS)
- Dimensions, housing W x H x D: 202 x 230 x 70 mm
- Protection class: IP 30 (EN 60529)
- Alarm sound: Min. 70 dB(A)
- Replaces: LAZ 04-3


For more information see Downloads


OEG no. 118307820
Manufacturer Afriso
Manufacturer number 43755
EAN 4016203437556
Weight [kg] 1.8
Notes
CE

CE

CE
Customs tariff number 85318070
en
Question

Wann braucht man Hochvakuum, wann Niedrigvakuum?

Answer OEG:

Guten Tag,


Hochvakuum sagt man bei Druck bis zirka - 400 mbar im Tank. Niedrigvakuum sagt man bis -70 mbar Druck im Tank.
In der normalen Öltanktechnik wird Niedrigvakuum verwendet.

Ein schönes Wochenende wünscht das OEG TEAM

You have to be logged in to ask a question

Average customer assessment
Bewertungen
en 14/02/2017, 14:15:33 of: Mr Feld

gut

Ein Leckanzeigegerät von Afriso einfach Top

In order to give a review, you have to be logged in.