You are using an outdated browser. Please update your browser now to display the page correctly.
Oil burner control unit for controlling two-stage forced-draught oil burners in intermittent operation. The control system monitors the flame and ensures reliable safety shutdown in the event of a fault.
All product informationOil burner control unit for controlling two-stage forced-draught oil burners in intermittent operation. The control system monitors the flame and ensures reliable safety shutdown in the event of a fault.
| Suitable for: | ||
|
|
Control unit with photoconductive cell and cable |
|
For more information see Downloads
| OEG no. | 150132255 |
| Voltage [V]: | 230 |
| Protection type [IP]: |
IP44 |
| Safety time [s]: | 10 |
| European standard: | 230 |
| Pre-purge time: | 12 seconds |
| Post-ignition time: | 20 seconds |
| Pre-ignition time: | 12 seconds |
| Power consumption: | 5 VA |
| Ambient temperature [°C]: | 0 .. 60 |
| Manufacturer | Honeywell |
| Manufacturer number | 02431U |
| EAN | 4046911021419 |
| Also replaces |
|
| Weight [kg] | 0.16 |
| Customs tariff number | 85364900 (HU) |