The Orkli motorised zone valves with limit switches are suitable for the use in primary circuits of solar systems and heating systems. The 2-way zone valves can be used for water with a glycol content of up to 50%...
All product informationThe Orkli motorised zone valves with limit switches are suitable for the use in primary circuits of solar systems and heating systems. The 2-way zone valves can be used for water with a glycol content of up to 50%.
Replaces:
30320200
For more information see Downloads
| OEG no. | 516100040 |
| Connection size: | 1" IT |
| Auxiliary switch: | Yes |
| Voltage [V]: | 230 |
| Media temperature [°C]: | -20 .. 160 |
| Pressure max. [bar]: | 10 |
| Power consumption [W]: | 5 |
| Closing time [s]: | 5 |
| Opening time [s]: | 12 |
| Media: | Water with up to 50 % glycol |
| Housing: | Brass |
| Seal: | EPDM |
| Cable length [mm]: | 600 |
| Manufacturer | Orkli |
| Herstellernummer | 30323200 |
| Also replaces |
|
| Weight [kg] | 1 |
| Customs tariff number | 85011093 (EE) |
Sluit dit ventiel veerbelast of is er nog een schakelfase nodig om van open naar gesloten toestand te gaan? M.a.w. zodra de spanning wegvalt gaat de klep dan automatisch sluiten?
Er is geen omschakelcontact nodig. De klep sluit door een veer. Let op het maximale drukverschil en de doorstroomsnelheid. Deze 1"-uitvoering maakt een maximaal drukverschil van 0,7 bar en een Kvs-waarde van 6,2 m³/h mogelijk.