Leak protection system for leak monitoring in oil sump pans, inspection shafts and protective conduits. The integrated shock-proof socket interrupts the power supply as soon as fluid is detected on the sensor...
All product informationLeak protection system for leak monitoring in oil sump pans, inspection shafts and protective conduits. The integrated shock-proof socket interrupts the power supply as soon as fluid is detected on the sensor. Suitable for diesel and heating oils, FAME, urea solution (ADBlue) and oil/water mixtures.
For more information see Downloads
| OEG no. | 120540230 |
| Voltage [V]: | 230 V AC |
| Current [A]: | 8 |
| Protection type [IP]: |
IP20 |
| Ambient temperature [°C]: | -20 .. 60 |
| Switching capacity [W]: | 1,800 |
| Cable length: | 2 |
| Weight [kg] | 0.56 |
| Customs tariff number | 85319000 |
Ist der Leckagemelder 120540230 in Verbindung mit Ölauffanwanne AW1 oder AW 3 zugelassen als Auffanwanne mit Sondenüberwachung zum Abschalten des Brenners im Havariefall gemäß TRwS 791 Punkt 7.1.3 Abs. 2 ?
Guten Tag,
der Artikel ist aufgrund der Schnurr/Stecker Verbindung in dem Fall ungeeignet. Bitte verwenden Sie unseren Artikel Oil/water alarm ÖWWG 3 with burner connection set (Zulassungsnummer Z-65.40-339) in Verbindung mit einer der von Ihnen genannten Ölauffangwanne.