The thermocouple is part of the thermoelectric flame failure device, which is responsible to prevent the escape of unburnt gas in case of failure. This is achieved by the thermoelectric characteristic...
All product information Scope of deliveryThe thermocouple is part of the thermoelectric flame failure device, which is responsible to prevent the escape of unburnt gas in case of failure. This is achieved by the thermoelectric characteristic of the thermocouple and the magnetic characteristic of the magnetic unit inside the gas safety valve.
Technical features:
• Switching times: opening 1 to 3 seconds, closing 60 to 90 seconds
• Max. tightening torque: 3 Nm
• Voltage yield: approx. 5.5 mV / 100°C, max. approx. 30 mV
• Max. temperature at the tip: approx. +650°C
• Max. temperature hard soldering point: approx. +400°C
• Max. temperature soft soldering point: approx. +220°C
• Materials: positive leg Ni90Cr10, negative leg constantan
• 11/32" connection
| Scope of delivery: | |||
| 1 x | thermocouple | ||
| 6 x | adapter | ||
| OEG no. | 133465000 |
| Length [mm]: | 900 |
| Manufacturer | OEG |
| Also replaces |
|
| Weight [kg] | 0.05 |
| Customs tariff number | 90251900 (ES) |
Bonjour ma question est , est-il utilisable sur du propane ou gaz de ville ou les deux ? car mes autres fournisseurs eux il faut choisir le type de gaz .
pour tout type de gaz
bonjour je suis a la recherche de thermocouple pour du propane ou gpl avez vous quelque chose ? Cordialement
Les thermocouples sont indépendants du gaz utilisé.